Electrical & Automation • Surge Protective Devices (SPD)
Taxnele TXSA-60 AC Surge Protective Device, 4P, 60kA, DIN Rail Mounting
Taxnele TXSA-60 4P is an AC surge protective device (SPD) designed to protect three-phase electrical installations with a neutral conductor against transient overvoltages, voltage impulses and indirect lightning effects. The device features a 4P configuration, L-L-L-N terminals, Uc 275V AC per pole, Imax 60kA, In 30kA, Up ≤ 2.2kV and DIN rail mounting.
SPD for AC Networks4P L-L-L-NImax 60kAIn 30kADIN Rail Mounting
Product Description
The Taxnele TXSA-60 4P AC surge protective device is an SPD intended to protect low-voltage electrical installations, particularly three-phase networks with a neutral conductor. It is installed on a DIN rail within the electrical distribution board and helps limit voltage spikes that may occur in the electrical network.
The 4P version is designed to protect phases L1, L2, L3 and the N conductor. The L-L-L-N terminal configuration allows integration into three-phase electrical distribution boards with a neutral conductor, where voltage impulses need to be diverted to the earthing system.
The main technical ratings are Uc 275V AC per pole, Imax 60kA, In 30kA and Up ≤ 2.2kV. The front indicator allows visual checking of each module's status, helping quickly identify situations where the surge protective device requires inspection or replacement.
The surge protective device must be installed by an authorised electrician or qualified personnel in accordance with the distribution board wiring diagram, applicable technical standards, the manufacturer's instructions and the earthing system requirements.
4P
Three-Phase Protection with Neutral
The 4P configuration allows protection of the L1, L2, L3 and N conductors in three-phase electrical networks with a neutral conductor.
60kA
Maximum Current of 60kA
The maximum discharge current Imax of 60kA supports protection of the installation against powerful surge impulses.
DIN
DIN Rail Mounting
The modular construction allows integration into standard electrical distribution boards on a DIN rail by qualified personnel.
Main Benefits
Protection for three-phase electrical installations with a neutral conductor.
Protection for phases L1, L2, L3 and the N conductor.
Limits transient overvoltages within the electrical distribution board.
Protection against voltage impulses and indirect lightning effects.
Maximum discharge current Imax of 60kA.
Nominal discharge current In of 30kA.
Voltage protection level Up ≤ 2.2kV.
Front indicator for checking the device's status.
Recommended Applications
Three-phase electrical distribution boards with a neutral conductor.
Homes with a three-phase supply.
Commercial premises and offices.
Workshops, garages and technical areas.
Low-voltage electrical installations.
Circuits containing electrical equipment sensitive to voltage impulses.
Taxnele TXSA-60 4P Technical Specifications
Product Type
AC surge protective device / SPD
Brand
Taxnele
Model
TXSA-60
Commercial Name
TXSA-60KA / TXSA-60, 4P, 60kA
Number of Poles
4P
Terminal Configuration
L-L-L-N
Network Type
AC, three-phase with neutral
Maximum Continuous Operating Voltage
Uc 275V AC per pole
Nominal Discharge Current
In 30kA
Maximum Discharge Current
Imax 60kA
Voltage Protection Level
Up ≤ 2.2kV
Standard Marked on the Product
IEC 61643-1
Conformity Marking
CE
Status Indicator
Front indicator for checking each module's status
Mounting
DIN rail, within an electrical distribution board
Use
Protection against transient overvoltages and voltage impulses
Applications
Electrical distribution boards, three-phase installations, homes, commercial premises and technical areas
Category
Electrical & Automation
Subcategory
Electrical Protection / Surge Protective Devices (SPD)
Frequently Asked Questions About the Taxnele TXSA-60 4P Surge Protective Device
What is Taxnele TXSA-60 4P?
Taxnele TXSA-60 4P is an AC surge protective device (SPD) used to limit transient overvoltages and voltage impulses in three-phase electrical installations with a neutral conductor.
Which installations is the 4P model suitable for?
The 4P model is suitable for three-phase electrical installations with a neutral conductor, where protection of the L1, L2, L3 and N conductors is required.
Where is this surge protective device installed?
The device is installed on a DIN rail within the electrical distribution board, in accordance with the wiring diagram and installation instructions.
What is its maximum discharge current?
The Taxnele TXSA-60 4P model has a maximum discharge current Imax of 60kA and a nominal discharge current In of 30kA.
What is its voltage protection level?
The voltage protection level is Up ≤ 2.2kV, according to the model's specifications.
What is the purpose of the front indicator?
The front indicator allows visual checking of each module's status and helps identify situations where the device needs to be inspected or replaced.
Can anyone install it?
No. Installation must be carried out by an authorised electrician or qualified personnel in accordance with applicable electrical standards and the distribution board wiring diagram.
60kA SPD Protection for Three-Phase Installations with Neutral
Taxnele TXSA-60 4P offers a compact solution for protecting three-phase electrical installations against transient overvoltages, with DIN rail mounting, a 4P L-L-L-N configuration, Uc 275V AC per pole, Imax 60kA, In 30kA and a protection level Up ≤ 2.2kV.